HGL serieko karga-isolamendu etengailuak fidagarritasunez funtziona dezake baldintza hauetan:
| Ith korronte termiko konbentzionala (A) | 63A | 100A | 160A | 250A | 630A | 1600A | 3150A | |||||||||||||
| In-ko korronte nominala (A) | 40 | 63 | 80 | 100 | 125 | 160 | 200 | 250 | 315 | 400 | 500 | 630 | 1000 | 1250 | 1600 | 2000 | 2500 | 3150 | ||
| Ui-ren bulkada-tentsio nominala (kV) | 750 | 750 | 750 | 750 | 750 | 750 | 750 | 750 | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 | ||
| Erresistentzia dielektrikoa (kV) | 5000 | 5000 | 5000 | 5000 | 5000 | 5000 | 5000 | 5000 | 8000 | 8000 | 8000 | 8000 | 10000 | 10000 | 10000 | 10000 | 10000 | 10000 | ||
| Tentsio nominalaren igoera-tentsioa Uimp (kV) (Instalazio kategoria IV) | 6 | 6 | 6 | 6 | 8 | 8 | 8 | 8 | 12 | 12 | 12 | 12 | 12 | 12 | 12 | 12 | 12 | 12 | ||
| Laneko korronte nominala (A) | 380V | AC-21 | 40 | 63 | 80 | 100 | 125 | 160 | 200 | 250 | 315 | 400 | 500 | 630 | 1000 | 1250 | 1600 | 2000 | 2500 | 3150 |
| AC-22 | 40 | 63 | 80 | 100 | 125 | 160 | 200 | 250 | 315 | 400 | 500 | 630 | 1000 | 1250 | 1600 | 2000 | 2000 | 3150 | ||
| AC-23 | 40 | 63 | 80 | 100 | 125 | 160 | 200 | 250 | 315 | 340 | 425 | 536 | ||||||||
| 660V | AC-21 | 40 | 50 | 80 | 80 | 125 | 160 | 200 | 250 | 315 | 400 | 400 | 500 | 1000 | 1000 | 1600 | 2000 | 2500 | 2500 | |
| AC-22 | 32 | 32 | 50 | 50 | 125 | 160 | 160 | 160 | 315 | 315 | 315 | 315 | 800 | 800 | 800 | 1000 | 1000 | 1000 | ||
| AC-23 | 25 | 25 | 40 | 40 | 80 | 80 | 100 | 125 | 125 | 125 | 125 | 125 | ||||||||
| 220V | DC-21 | 40 | 63 | 80 | 100 | 125 | 160 | 200 | 250 | 315 | 400 | 500 | 630 | 1000 | 1250 | 1600 | 2000 | 2500 | 2500 | |
| DC-22 | 40 | 63 | 80 | 80 | 125 | 160 | 200 | 250 | 315 | 400 | 400 | 500 | 1000 | 1250 | 1250 | 1600 | 1600 | 1600 | ||
| DC-23 | 40 | 63 | 63 | 63 | 125 | 125 | 160 | 200 | ||||||||||||
| 440V | DC-21 | 100 | 125 | 160 | 200 | 315 | 400 | 400 | 500 | 1000 | 1250 | 1250 | 2000 | 2000 | 2000 | |||||
| DC-22 | 100 | 125 | 160 | 200 | 315 | 400 | 400 | 500 | 1000 | 1250 | 1250 | 1250 | 1250 | 1250 | ||||||
| DC-23 | 100 | 125 | 160 | 200 | 315 | 400 | 400 | 500 | 1000 | 1000 | 1000 | |||||||||
| Motorraren potentzia P (KV) | 380V | 18,5 | 25 | 40 | 40 | 63 | 80 | 100 | 132 | 160 | 220 | 280 | 315 | 560 | 560 | 560 | 710 | 710 | 710 | |
| 660V | 22 | 22 | 33 | 33 | 75 | 75 | 90 | 110 | 185 | 185 | 185 | 185 | 475 | 475 | 475 | 750 | 750 | 750 | ||
| Icw denbora laburreko korronte nominala (kA rms) 0.1s/1.0s | 10/5 | 10/5 | 10/5 | 10/5 | 20/10 | 20/10 | 30/12 | 30/12 | 45/20 | 45/20 | 50/25 | 50/25 | 90/50 | 90/50 | 90/50 | 90/50 | 90/50 | 90/50 | ||
| Icn haustura-ahalmen nominala (A rms) AC23 380V | 320 | 504 | 640 | 800 | 1000 | 1000 | 1600 | 1600 | 2500 | 3200 | 3200 | 3200 | ||||||||
| Icm-ko potentzia nominala (A rms) AC23 380V | 400 | 630 | 800 | 1000 | 1250 | 1250 | 2000 | 2000 | 3150 | 4000 | 4000 | 4000 | ||||||||
| Zirkuitulaburreko itxiera-ahalmen nominala Icm (kA gailurra) | 7.5 | 7.5 | 10 | 10 | 12 | 12 | 17 | 17 | 30 | 30 | 40 | 40 | ||||||||
| Iraunkortasun mekanikoa (funtzionamendu-ziklo kopurua) | 10000 | 10000 | 10000 | 10000 | 10000 | 10000 | 10000 | 10000 | 5500 | 5500 | 5500 | 5500 | 4000 | 4000 | 3000 | |||||
| Iraunkortasun elektrikoa (funtzionamendu-ziklo kopurua) Ue = 660 V, Ie korronte nominala | C0SΦ=0.95 AC21 | 1700 | 1700 | 1700 | 1700 | 1500 | 1500 | 1500 | 1500 | 750 | 750 | 750 | 750 | 600 | 600 | 450 | 2500 | 2500 | 2500 | |
| COSΦ=0.65 AC22 | 100 | 100 | 100 | 100 | 1000 | 1000 | 1000 | 1000 | 500 | 500 | 500 | 500 | 400 | 400 | 300 | |||||
| C0SΦ=0.35 AC23 | 500 | 500 | 500 | 500 | 500 | 500 | 500 | 500 | 250 | 250 | 250 | 250 | 200 | 200 | 150 | |||||
| Funtzionamendu-momentua (Nm) | 1.2 | 1.2 | 1.2 | 1.2 | 6.5 | 6.5 | 10 | 10 | 14.5 | 14.5 | 14.5 | 14.5 | 37 | 37 | 60 | 60 | 60 | 60 | ||